Transformers of transformer substation MT/BT are used to reduce the voltage from medium to low, then to feed a group of loads. Usually they are chosen and dimensioned according to the loads to be supplied but it can happen that in certain situations there is an increase of power and consequently the generations of overcurrents. These overcurrents are harmful for the transformer insulation and its fast degradation leads to the decrease of its life and use. In this thesis this subject is analyzed starting from the thermal model of the transformer, and through the use of an algorithm is shown the trend of the hot spot temperature in certain operating conditions (normal, overload and at different environmental temperatures). For each of this situations it is also highlighted the loss of life of the transformer. Another topic treated is the implementation of the thermal model in overloads protection, by comparing the normal thermal relays with the most reliable thermal image relays.

I trasformatori delle cabine di trasformazione MT/BT servono per ridurre la tensione da media a bassa per poi alimentare un gruppo di carichi. Di solito vengono scelti e dimensionati sulla base dei carichi da alimentare, ma può succedere che in determinate situazioni ci sia un aumento della potenza e di conseguenza la generazione di sovracorrenti. Queste sovracorrenti sono dannose per l’isolante del trasformatore, e un suo veloce degrado porta alla diminuzione di vita e di utilizzo. In questa tesi viene analizzato questo argomento partendo dal modello termico del trasformatore e tramite l’utilizzo di un algoritmo viene mostrato l’andamento della temperatura del punto caldo in determinate condizioni di funzionamento (normale, sovraccarico e a diverse temperature ambientali). Per ognuna di queste situazioni inoltre, viene messa in risalto la perdita di vita del trasformatore. Altro aspetto trattato è l’implementazione del modello termico nelle protezioni contro le sovracorrenti, mettendo a confronto i normali relè termici con i più affidabili relè ad immagine termica.

Applicazioni del modello termico del trasformatore alle stazioni di trasformazione MT/BT

COGLIANO, LORENZO;CORE, ANDREA
2014/2015

Abstract

Transformers of transformer substation MT/BT are used to reduce the voltage from medium to low, then to feed a group of loads. Usually they are chosen and dimensioned according to the loads to be supplied but it can happen that in certain situations there is an increase of power and consequently the generations of overcurrents. These overcurrents are harmful for the transformer insulation and its fast degradation leads to the decrease of its life and use. In this thesis this subject is analyzed starting from the thermal model of the transformer, and through the use of an algorithm is shown the trend of the hot spot temperature in certain operating conditions (normal, overload and at different environmental temperatures). For each of this situations it is also highlighted the loss of life of the transformer. Another topic treated is the implementation of the thermal model in overloads protection, by comparing the normal thermal relays with the most reliable thermal image relays.
ING - Scuola di Ingegneria Industriale e dell'Informazione
28-lug-2015
2014/2015
I trasformatori delle cabine di trasformazione MT/BT servono per ridurre la tensione da media a bassa per poi alimentare un gruppo di carichi. Di solito vengono scelti e dimensionati sulla base dei carichi da alimentare, ma può succedere che in determinate situazioni ci sia un aumento della potenza e di conseguenza la generazione di sovracorrenti. Queste sovracorrenti sono dannose per l’isolante del trasformatore, e un suo veloce degrado porta alla diminuzione di vita e di utilizzo. In questa tesi viene analizzato questo argomento partendo dal modello termico del trasformatore e tramite l’utilizzo di un algoritmo viene mostrato l’andamento della temperatura del punto caldo in determinate condizioni di funzionamento (normale, sovraccarico e a diverse temperature ambientali). Per ognuna di queste situazioni inoltre, viene messa in risalto la perdita di vita del trasformatore. Altro aspetto trattato è l’implementazione del modello termico nelle protezioni contro le sovracorrenti, mettendo a confronto i normali relè termici con i più affidabili relè ad immagine termica.
Tesi di laurea Magistrale
File allegati
File Dimensione Formato  
Applicazione del modello termico del trasformatore alle stazioni di trasformazione MT_BT.pdf

accessibile in internet solo dagli utenti autorizzati

Descrizione: Testo della tesi
Dimensione 2.19 MB
Formato Adobe PDF
2.19 MB Adobe PDF   Visualizza/Apri

I documenti in POLITesi sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/10589/108888