The object of this dissertation is the plant-building dynamic simulation of a new office building, in Vizzola Ticino, since the building aims at the LEED certification. More in detail, following a short description of the LEED certification and of the case study, it is performed the verification of the “Energy Minimum Performance” prerequisite, by mean of a quantification of the points which could be earned under the “Optimize Energy Performance” credit; both this credits are included in the “Energy and Atmosphere“ section of the LEED protocol and they are aimed at the energy efficency. In order to achieve the highest evaluation under the Optimize Energy Performance credit, the dynamic simulation must comply with the LEED protocol “Reference Guide for Building Design and Construction” [1]; moreover, it must also comply with the Performance Rating Method included in the appendix G of the ASHRAE 90.1-2010 legislation [2]. The method mentioned above is based on the production of two models: the Proposed Building, which consider the real building with its plant and the Baseline Buildings, which consider the standard building, modelled according to some criteria included in the appendix G of the ASHRAE legislation [2]. The simulation is performed producing the two different models, by mean of the software of dynamic simulation IES-VE, then it will be compared their energy use. The compliance with the “Energy Minimum Performance” is verified, since it is observed a significant improvement in the primary energy use, exspressed in kWh per year, in fact the energy use of the Baseline Building is 5% higher. The Optimize Energy performance will be argued in a report describing the achieved results which will be largely commented. The conclusion of this dissertation includes a detailed description of the results achieved, the structural and plant engineering differences between the two models are compared in order to produce a rational criticism.

L’oggetto della presente trattazione riguarda la simulazione dinamica edificio-impianto relativa ad un edificio per uffici di nuova costruzione situato a Vizzola Ticino, ai fini della certificazione LEED. Nel dettaglio, dopo una breve descrizione della certificazione LEED e la presentazione del caso studio, verrà trattata la verifica del prerequisito “Energy Minimum Performance” e verranno quantificati i punti ottenibili dal credito: “Optimize Energy Performance”; Entrambi i crediti appartenenti alla sezione: “energia e atmosfera” del protocollo LEED sono svolti a promuovere l’efficientamento energetico. Per ottenere il massimo punteggio possibile dell’Optimize Energy Performance è necessario realizzare una simulazione dinamica come descritto nel protocollo LEED “Reference Guide for Building Design and Construction” [1], seguendo il Performance Rating Method contenuto nell’appendice G della normativa ASHRAE 90.1-2010 [2]. Il metodo si basa sulla costruzione di due modelli: il Proposed Building, ovvero l’edificio reale con il suo impianto e il Baseline Building, l’edificio di riferimento modellato secondo i criteri riportati nell’appendice G della normativa ASHRAE [2]. La simulazione sarà effettuata costruendo i due differenti modelli tramite il software di simulazione dinamica IES-VE, confrontandone poi i consumi energetici. Perché sia rispettato il prerequisito “Energy Minimum Performance”, verrà verificato un miglioramento nel consumo di energia primaria espresso in kWh/annui, di almeno il 5% rispetto al consumo del Baseline Building. Per quanto riguarda l’Optimize Energy Performance verrà prodotto un report con i risultati ottenuti che saranno adeguatamente commentati. Infine si analizzeranno i risultati ottenuti, evidenziando le differenze tra i due modelli sia strutturali che impiantistiche riportandone una critica razionale.

Simulazione dinamica edificio-impianto dell'MXP Buisness Park di vodafone al fine dell'ottenimento dei crediti LEED

PAVESI, STEFANO
2016/2017

Abstract

The object of this dissertation is the plant-building dynamic simulation of a new office building, in Vizzola Ticino, since the building aims at the LEED certification. More in detail, following a short description of the LEED certification and of the case study, it is performed the verification of the “Energy Minimum Performance” prerequisite, by mean of a quantification of the points which could be earned under the “Optimize Energy Performance” credit; both this credits are included in the “Energy and Atmosphere“ section of the LEED protocol and they are aimed at the energy efficency. In order to achieve the highest evaluation under the Optimize Energy Performance credit, the dynamic simulation must comply with the LEED protocol “Reference Guide for Building Design and Construction” [1]; moreover, it must also comply with the Performance Rating Method included in the appendix G of the ASHRAE 90.1-2010 legislation [2]. The method mentioned above is based on the production of two models: the Proposed Building, which consider the real building with its plant and the Baseline Buildings, which consider the standard building, modelled according to some criteria included in the appendix G of the ASHRAE legislation [2]. The simulation is performed producing the two different models, by mean of the software of dynamic simulation IES-VE, then it will be compared their energy use. The compliance with the “Energy Minimum Performance” is verified, since it is observed a significant improvement in the primary energy use, exspressed in kWh per year, in fact the energy use of the Baseline Building is 5% higher. The Optimize Energy performance will be argued in a report describing the achieved results which will be largely commented. The conclusion of this dissertation includes a detailed description of the results achieved, the structural and plant engineering differences between the two models are compared in order to produce a rational criticism.
TRUCCOLO, REDY ALESSANDRO
ING - Scuola di Ingegneria Industriale e dell'Informazione
19-apr-2018
2016/2017
L’oggetto della presente trattazione riguarda la simulazione dinamica edificio-impianto relativa ad un edificio per uffici di nuova costruzione situato a Vizzola Ticino, ai fini della certificazione LEED. Nel dettaglio, dopo una breve descrizione della certificazione LEED e la presentazione del caso studio, verrà trattata la verifica del prerequisito “Energy Minimum Performance” e verranno quantificati i punti ottenibili dal credito: “Optimize Energy Performance”; Entrambi i crediti appartenenti alla sezione: “energia e atmosfera” del protocollo LEED sono svolti a promuovere l’efficientamento energetico. Per ottenere il massimo punteggio possibile dell’Optimize Energy Performance è necessario realizzare una simulazione dinamica come descritto nel protocollo LEED “Reference Guide for Building Design and Construction” [1], seguendo il Performance Rating Method contenuto nell’appendice G della normativa ASHRAE 90.1-2010 [2]. Il metodo si basa sulla costruzione di due modelli: il Proposed Building, ovvero l’edificio reale con il suo impianto e il Baseline Building, l’edificio di riferimento modellato secondo i criteri riportati nell’appendice G della normativa ASHRAE [2]. La simulazione sarà effettuata costruendo i due differenti modelli tramite il software di simulazione dinamica IES-VE, confrontandone poi i consumi energetici. Perché sia rispettato il prerequisito “Energy Minimum Performance”, verrà verificato un miglioramento nel consumo di energia primaria espresso in kWh/annui, di almeno il 5% rispetto al consumo del Baseline Building. Per quanto riguarda l’Optimize Energy Performance verrà prodotto un report con i risultati ottenuti che saranno adeguatamente commentati. Infine si analizzeranno i risultati ottenuti, evidenziando le differenze tra i due modelli sia strutturali che impiantistiche riportandone una critica razionale.
Tesi di laurea Magistrale
File allegati
File Dimensione Formato  
2018_04_Pavesi.pdf

accessibile in internet per tutti

Dimensione 4.56 MB
Formato Adobe PDF
4.56 MB Adobe PDF Visualizza/Apri

I documenti in POLITesi sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/10589/139606