This thesis describes the fault protection system and the monitoring system for the low voltage power distribution network of a water treatment plant. Protection coorditation is based on directional logic selectivity. The IEC61850 protocol is used for both protection and monitoring: vertical and horizontal communication are employed by using GOOSE messages and Report Control Blocks (RCB) for the communication among the smart low voltage circuit breakers that were used throughout the plant. Logic selectivity was implemented by using ABB hardware and software, and the monitoring system was developed using the Zenon SCADA. The complete system was built and tested through simulations implemented with the LabVIEW software. The results obtained were satisfactory according with the proposed objectives.

Questa tesi descrive il sistema di protezione e supervisione della rete elettrico di un impianto di trattamento acque. Il sistema di protezione è basato su selettività logica direzionale. Il protocollo IEC61850 è stato utilizzato sia per la protezione che per la supervisione: si impiegano schemi di comunicazione orizzontale e verticale attraverso messaggi GOOSE e RCB (Report Control Block) che connettono gli interruttori utilizzati come apparecchi di protezione nell'impianto. La selettività logica è stata realizzata con hardware e software ABB, mentre il sistema di supervisione utilizza la piattaforma SCADA Zenon. Il sistema è stato implementato e poi testato attraverso simulazioni realizzate con LabVIEW, e i risultati ottenuti sono stati conformi ai requisiti di progetto.

Implementation of logic directional selectivity and monitoring system in low voltage electrical installation using IEC61850

RINCÓN NÚÑEZ, JEINSON DAVID
2018/2019

Abstract

This thesis describes the fault protection system and the monitoring system for the low voltage power distribution network of a water treatment plant. Protection coorditation is based on directional logic selectivity. The IEC61850 protocol is used for both protection and monitoring: vertical and horizontal communication are employed by using GOOSE messages and Report Control Blocks (RCB) for the communication among the smart low voltage circuit breakers that were used throughout the plant. Logic selectivity was implemented by using ABB hardware and software, and the monitoring system was developed using the Zenon SCADA. The complete system was built and tested through simulations implemented with the LabVIEW software. The results obtained were satisfactory according with the proposed objectives.
ING - Scuola di Ingegneria Industriale e dell'Informazione
3-ott-2019
2018/2019
Questa tesi descrive il sistema di protezione e supervisione della rete elettrico di un impianto di trattamento acque. Il sistema di protezione è basato su selettività logica direzionale. Il protocollo IEC61850 è stato utilizzato sia per la protezione che per la supervisione: si impiegano schemi di comunicazione orizzontale e verticale attraverso messaggi GOOSE e RCB (Report Control Block) che connettono gli interruttori utilizzati come apparecchi di protezione nell'impianto. La selettività logica è stata realizzata con hardware e software ABB, mentre il sistema di supervisione utilizza la piattaforma SCADA Zenon. Il sistema è stato implementato e poi testato attraverso simulazioni realizzate con LabVIEW, e i risultati ottenuti sono stati conformi ai requisiti di progetto.
Tesi di laurea Magistrale
File allegati
File Dimensione Formato  
2019_10_Rincon.pdf

non accessibile

Descrizione: Thesis text
Dimensione 2.97 MB
Formato Adobe PDF
2.97 MB Adobe PDF   Visualizza/Apri

I documenti in POLITesi sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.