The integration of floating photovoltaic systems with existing pumped hydro storage plants couples solar electricity generation with large-scale, long-duration energy storage. The FPV array supplies power that can be sold to the grid or used directly to drive the pumps, while the reservoir provides the dual function of energy storage and a cooling medium that enhances module efficiency. Despite growing research interest, the existing literature lacks a globally representative assessment that accounts for the diversity of electricity market designs and the systematic treatment of turbomachinery part-load behavior. This thesis presents the first multi-continent, multi-market, high-resolution techno-economic assessment of FPV–PHS integration. A unified mixed-integer linear programming model is developed and applied to 17 PHS facilities across Europe, North America, South America, Asia, Oceania, and Africa, operating under five distinct market architectures: zonal day-ahead markets, nodal locational marginal pricing, regional gross pool markets, regulated tariff regimes, and hybrid regulated–contractual systems. The model incorporates hourly meteorological, hydrological, and electricity price data for the full year 2023, piecewise-linear approximations of head-dependent pump and turbine efficiency curves, and a dynamic water balance accounting for evaporation and precipitation. The analysis focuses on a fully integrated configuration in which FPV electricity can be flexibly allocated between driving the pumps and direct grid export. The results demonstrate that electricity market design is the primary determinant of economic viability. In liberalized markets with high price volatility and pronounced diurnal spreads, notably Italy, Spain, Japan, and the Australian National Electricity Market, the integrated plants achieve strongly positive net present values, ranging from 16 to 684 MEUR, with payback times between 2.1 and 10.1 years. In regulated tariff and low-price markets, including Ontario in Canada, PJM in the United States, China, South Africa, India, and Argentina, the net present values are predominantly negative, ranging from –48 to –203 MEUR, as the absence of sufficient price spreads precludes profitable pumped storage arbitrage. Physical characteristics, such as rated head and pump modularity, condition the ability of a plant to capture available market opportunities, but no physical parameter alone predicts success. A Market–IPP screening framework that combines a market revenue metric with the Integration Potential Parameter is proposed as a practical tool for identifying retrofit candidates across the global PHS fleet. The thesis concludes that FPV–PHS integration is an economically attractive retrofit strategy in liberalized high-volatility markets, while regulatory reforms, such as the introduction of time-of-use pricing or capacity remuneration mechanisms, are a prerequisite for unlocking this potential in regulated environments.

L’integrazione dei sistemi fotovoltaici galleggianti (Floating Photovoltaics, FPV) con gli impianti idroelettrici ad accumulo mediante pompaggio (Pumped Hydro Storage, PHS) esistenti consente di combinare la generazione di energia solare con sistemi di accumulo energetico su larga scala e di lunga durata. L’impianto FPV fornisce energia elettrica che può essere immessa in rete oppure utilizzata direttamente per alimentare le pompe, mentre il bacino svolge una duplice funzione: accumulo di energia e mezzo di raffreddamento, contribuendo così ad aumentare l’efficienza dei moduli fotovoltaici. Nonostante il crescente interesse scientifico per questa soluzione, la letteratura esistente non dispone di una valutazione globale rappresentativa che tenga conto della diversità delle strutture dei mercati elettrici e di una trattazione sistematica del comportamento delle turbomacchine in condizioni di carico parziale. La presente tesi propone la prima valutazione tecno-economica ad alta risoluzione, multi-continentale e multi-mercato dell’integrazione FPV–PHS. A tal fine, è stato sviluppato un modello unificato di programmazione lineare mista intera (Mixed-Integer Linear Programming, MILP), applicato a 17 impianti PHS distribuiti in Europa, Nord America, Sud America, Asia, Oceania e Africa, operanti nell’ambito di cinque differenti architetture di mercato: mercati zonali del giorno prima (day-ahead), mercati nodali basati sul prezzo marginale localizzato (Locational Marginal Pricing, LMP), mercati regionali di tipo gross pool, regimi tariffari regolati e sistemi ibridi regolati–contrattuali. Il modello integra dati orari meteorologici, idrologici e dei prezzi dell’energia elettrica relativi all’intero anno 2023, approssimazioni lineari a tratti delle curve di rendimento di pompe e turbine dipendenti dal salto idraulico, nonché un bilancio idrico dinamico che considera evaporazione e precipitazioni. L’analisi si concentra su una configurazione completamente integrata, nella quale l’energia prodotta dall’impianto FPV può essere allocata in modo flessibile tra l’alimentazione delle pompe e l’esportazione diretta verso la rete elettrica. I risultati dimostrano che la struttura del mercato elettrico rappresenta il principale fattore determinante della sostenibilità economica del sistema. Nei mercati liberalizzati caratterizzati da elevata volatilità dei prezzi e marcate differenze intragiornaliere, in particolare in Italia, Spagna, Giappone e nel National Electricity Market australiano, gli impianti integrati conseguono valori attuali netti (Net Present Value, NPV) significativamente positivi, compresi tra 16 e 684 milioni di euro, con tempi di ritorno dell’investimento variabili tra 2,1 e 10,1 anni. Al contrario, nei mercati caratterizzati da tariffe regolamentate e bassi livelli di prezzo, tra cui Ontario (Canada), PJM (Stati Uniti), Cina, Sudafrica, India e Argentina, i valori attuali netti risultano prevalentemente negativi, compresi tra −48 e −203 milioni di euro, poiché l’assenza di adeguati differenziali di prezzo impedisce di realizzare profitti attraverso l’arbitraggio energetico degli impianti di accumulo mediante pompaggio. Le caratteristiche fisiche degli impianti, quali il salto idraulico nominale e la modularità delle stazioni di pompaggio, influenzano la capacità di cogliere le opportunità offerte dal mercato, ma nessun parametro fisico, considerato singolarmente, risulta sufficiente a prevederne il successo economico. Viene pertanto proposto un quadro di valutazione denominato Market–IPP Screening Framework, che combina un indicatore di redditività di mercato con l’Integration Potential Parameter (IPP), quale strumento pratico per l’identificazione dei candidati più promettenti per interventi di retrofit all’interno della flotta globale di impianti PHS. La tesi conclude che l’integrazione FPV–PHS costituisce una strategia di retrofit economicamente vantaggiosa nei mercati liberalizzati caratterizzati da elevata volatilità dei prezzi. Nei contesti regolati, invece, il pieno sfruttamento di tale potenziale richiede l’adozione di riforme normative, quali l’introduzione di tariffe differenziate in funzione dell’orario di utilizzo (time-of-use pricing) o di meccanismi di remunerazione della capacità.

Techno-economic analysis of integrated pumped hydroelectric-Floating Photovoltaic systems: regional analysis of the impact of different market schemes worldwide

Jia, Xingyu
2025/2026

Abstract

The integration of floating photovoltaic systems with existing pumped hydro storage plants couples solar electricity generation with large-scale, long-duration energy storage. The FPV array supplies power that can be sold to the grid or used directly to drive the pumps, while the reservoir provides the dual function of energy storage and a cooling medium that enhances module efficiency. Despite growing research interest, the existing literature lacks a globally representative assessment that accounts for the diversity of electricity market designs and the systematic treatment of turbomachinery part-load behavior. This thesis presents the first multi-continent, multi-market, high-resolution techno-economic assessment of FPV–PHS integration. A unified mixed-integer linear programming model is developed and applied to 17 PHS facilities across Europe, North America, South America, Asia, Oceania, and Africa, operating under five distinct market architectures: zonal day-ahead markets, nodal locational marginal pricing, regional gross pool markets, regulated tariff regimes, and hybrid regulated–contractual systems. The model incorporates hourly meteorological, hydrological, and electricity price data for the full year 2023, piecewise-linear approximations of head-dependent pump and turbine efficiency curves, and a dynamic water balance accounting for evaporation and precipitation. The analysis focuses on a fully integrated configuration in which FPV electricity can be flexibly allocated between driving the pumps and direct grid export. The results demonstrate that electricity market design is the primary determinant of economic viability. In liberalized markets with high price volatility and pronounced diurnal spreads, notably Italy, Spain, Japan, and the Australian National Electricity Market, the integrated plants achieve strongly positive net present values, ranging from 16 to 684 MEUR, with payback times between 2.1 and 10.1 years. In regulated tariff and low-price markets, including Ontario in Canada, PJM in the United States, China, South Africa, India, and Argentina, the net present values are predominantly negative, ranging from –48 to –203 MEUR, as the absence of sufficient price spreads precludes profitable pumped storage arbitrage. Physical characteristics, such as rated head and pump modularity, condition the ability of a plant to capture available market opportunities, but no physical parameter alone predicts success. A Market–IPP screening framework that combines a market revenue metric with the Integration Potential Parameter is proposed as a practical tool for identifying retrofit candidates across the global PHS fleet. The thesis concludes that FPV–PHS integration is an economically attractive retrofit strategy in liberalized high-volatility markets, while regulatory reforms, such as the introduction of time-of-use pricing or capacity remuneration mechanisms, are a prerequisite for unlocking this potential in regulated environments.
ING - Scuola di Ingegneria Industriale e dell'Informazione
22-lug-2026
2025/2026
L’integrazione dei sistemi fotovoltaici galleggianti (Floating Photovoltaics, FPV) con gli impianti idroelettrici ad accumulo mediante pompaggio (Pumped Hydro Storage, PHS) esistenti consente di combinare la generazione di energia solare con sistemi di accumulo energetico su larga scala e di lunga durata. L’impianto FPV fornisce energia elettrica che può essere immessa in rete oppure utilizzata direttamente per alimentare le pompe, mentre il bacino svolge una duplice funzione: accumulo di energia e mezzo di raffreddamento, contribuendo così ad aumentare l’efficienza dei moduli fotovoltaici. Nonostante il crescente interesse scientifico per questa soluzione, la letteratura esistente non dispone di una valutazione globale rappresentativa che tenga conto della diversità delle strutture dei mercati elettrici e di una trattazione sistematica del comportamento delle turbomacchine in condizioni di carico parziale. La presente tesi propone la prima valutazione tecno-economica ad alta risoluzione, multi-continentale e multi-mercato dell’integrazione FPV–PHS. A tal fine, è stato sviluppato un modello unificato di programmazione lineare mista intera (Mixed-Integer Linear Programming, MILP), applicato a 17 impianti PHS distribuiti in Europa, Nord America, Sud America, Asia, Oceania e Africa, operanti nell’ambito di cinque differenti architetture di mercato: mercati zonali del giorno prima (day-ahead), mercati nodali basati sul prezzo marginale localizzato (Locational Marginal Pricing, LMP), mercati regionali di tipo gross pool, regimi tariffari regolati e sistemi ibridi regolati–contrattuali. Il modello integra dati orari meteorologici, idrologici e dei prezzi dell’energia elettrica relativi all’intero anno 2023, approssimazioni lineari a tratti delle curve di rendimento di pompe e turbine dipendenti dal salto idraulico, nonché un bilancio idrico dinamico che considera evaporazione e precipitazioni. L’analisi si concentra su una configurazione completamente integrata, nella quale l’energia prodotta dall’impianto FPV può essere allocata in modo flessibile tra l’alimentazione delle pompe e l’esportazione diretta verso la rete elettrica. I risultati dimostrano che la struttura del mercato elettrico rappresenta il principale fattore determinante della sostenibilità economica del sistema. Nei mercati liberalizzati caratterizzati da elevata volatilità dei prezzi e marcate differenze intragiornaliere, in particolare in Italia, Spagna, Giappone e nel National Electricity Market australiano, gli impianti integrati conseguono valori attuali netti (Net Present Value, NPV) significativamente positivi, compresi tra 16 e 684 milioni di euro, con tempi di ritorno dell’investimento variabili tra 2,1 e 10,1 anni. Al contrario, nei mercati caratterizzati da tariffe regolamentate e bassi livelli di prezzo, tra cui Ontario (Canada), PJM (Stati Uniti), Cina, Sudafrica, India e Argentina, i valori attuali netti risultano prevalentemente negativi, compresi tra −48 e −203 milioni di euro, poiché l’assenza di adeguati differenziali di prezzo impedisce di realizzare profitti attraverso l’arbitraggio energetico degli impianti di accumulo mediante pompaggio. Le caratteristiche fisiche degli impianti, quali il salto idraulico nominale e la modularità delle stazioni di pompaggio, influenzano la capacità di cogliere le opportunità offerte dal mercato, ma nessun parametro fisico, considerato singolarmente, risulta sufficiente a prevederne il successo economico. Viene pertanto proposto un quadro di valutazione denominato Market–IPP Screening Framework, che combina un indicatore di redditività di mercato con l’Integration Potential Parameter (IPP), quale strumento pratico per l’identificazione dei candidati più promettenti per interventi di retrofit all’interno della flotta globale di impianti PHS. La tesi conclude che l’integrazione FPV–PHS costituisce una strategia di retrofit economicamente vantaggiosa nei mercati liberalizzati caratterizzati da elevata volatilità dei prezzi. Nei contesti regolati, invece, il pieno sfruttamento di tale potenziale richiede l’adozione di riforme normative, quali l’introduzione di tariffe differenziate in funzione dell’orario di utilizzo (time-of-use pricing) o di meccanismi di remunerazione della capacità.
File allegati
File Dimensione Formato  
11010762_Jia_Xingyu_02-07-2026_Techno-economic Analysis of Integrated Pumped Hydroelectric-Floating Photovoltaic Systems.pdf

solo utenti autorizzati a partire dal 02/07/2027

Dimensione 18.04 MB
Formato Adobe PDF
18.04 MB Adobe PDF   Visualizza/Apri

I documenti in POLITesi sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/10589/259420