Power supply units (PSUs) in AI data centre racks must satisfy demanding dynamic current requirements, as the GPU loads they power transition between idle and peak states at sub-millisecond timescales. The OCP Diablo 400 specification defines eight dynamic pulse load profiles for PSU qualification testing in 800 V DC AI data centre racks, but provides no simulation tool for generating them nor is there a clearly established circuit model for these devices. This thesis designs and compares two Simulink implementations: an active model, based on a signal-flow with an integrator FCN architecture commanding a controlled current source, and a passive model, that uses a switched-resistance RL topology to generate its current profile. After a structural comparison, both models were quantitatively validated against three reference grids. While both models perform the same for slow profiles, the active model is clearly superior for fast, slew-rate-limited transients and is the recommendation for PSU qualification testing. The passive model is still essential for studies where bus dynamics and inductive transients are relevant.

Le unità di alimentazione (power supply units) nei rack dei data center per l'IA devono soddisfare requisiti di variazioni dinamiche della corrente estremamente esigenti, poiché i carichi delle GPU che alimentano passano dallo stato di riposo (idle) a quello di picco in scale temporali inferiori al millisecondo. La specifica OCP Diablo 400 definisce otto profili di carico dinamico impulsivo per i test di qualificazione delle PSU nei rack AI a 800 V DC, ma non fornisce alcuno strumento di simulazione per generarli, né esiste un modello circuitale chiaramente stabilito per questi dispositivi. L'obiettivo di questa tesi è quindi stato quello di presentare e confrontare due differenti implementazioni in Simulink: un modello attivo, basato su un flusso di segnale con architettura a integratore (FCN) che comanda una sorgente di corrente controllata, e un modello passivo, che utilizza una topologia RL a resistenza commutata per generare il proprio profilo di corrente. Dopo un confronto strutturale, entrambi i modelli sono stati validati quantitativamente rispetto a casi di riferimento. Sebbene entrambi i modelli offrano prestazioni analoghe per i profili lenti, il modello attivo è nettamente superiore per i transitori veloci limitati dallo slew-rate ed è la soluzione raccomandata per i test di qualificazione delle PSU. Il modello passivo rimane tuttavia essenziale per gli studi in cui la dinamica del bus e i transitori induttivi risultano rilevanti.

Electrical model of artificial intelligence infrastructure power supply unit

PARVU, IOANA-ANDREEA
2025/2026

Abstract

Power supply units (PSUs) in AI data centre racks must satisfy demanding dynamic current requirements, as the GPU loads they power transition between idle and peak states at sub-millisecond timescales. The OCP Diablo 400 specification defines eight dynamic pulse load profiles for PSU qualification testing in 800 V DC AI data centre racks, but provides no simulation tool for generating them nor is there a clearly established circuit model for these devices. This thesis designs and compares two Simulink implementations: an active model, based on a signal-flow with an integrator FCN architecture commanding a controlled current source, and a passive model, that uses a switched-resistance RL topology to generate its current profile. After a structural comparison, both models were quantitatively validated against three reference grids. While both models perform the same for slow profiles, the active model is clearly superior for fast, slew-rate-limited transients and is the recommendation for PSU qualification testing. The passive model is still essential for studies where bus dynamics and inductive transients are relevant.
ING - Scuola di Ingegneria Industriale e dell'Informazione
22-lug-2026
2025/2026
Le unità di alimentazione (power supply units) nei rack dei data center per l'IA devono soddisfare requisiti di variazioni dinamiche della corrente estremamente esigenti, poiché i carichi delle GPU che alimentano passano dallo stato di riposo (idle) a quello di picco in scale temporali inferiori al millisecondo. La specifica OCP Diablo 400 definisce otto profili di carico dinamico impulsivo per i test di qualificazione delle PSU nei rack AI a 800 V DC, ma non fornisce alcuno strumento di simulazione per generarli, né esiste un modello circuitale chiaramente stabilito per questi dispositivi. L'obiettivo di questa tesi è quindi stato quello di presentare e confrontare due differenti implementazioni in Simulink: un modello attivo, basato su un flusso di segnale con architettura a integratore (FCN) che comanda una sorgente di corrente controllata, e un modello passivo, che utilizza una topologia RL a resistenza commutata per generare il proprio profilo di corrente. Dopo un confronto strutturale, entrambi i modelli sono stati validati quantitativamente rispetto a casi di riferimento. Sebbene entrambi i modelli offrano prestazioni analoghe per i profili lenti, il modello attivo è nettamente superiore per i transitori veloci limitati dallo slew-rate ed è la soluzione raccomandata per i test di qualificazione delle PSU. Il modello passivo rimane tuttavia essenziale per gli studi in cui la dinamica del bus e i transitori induttivi risultano rilevanti.
File allegati
File Dimensione Formato  
2026_07_Parvu.pdf

accessibile in internet per tutti

Descrizione: Thesis file
Dimensione 2.23 MB
Formato Adobe PDF
2.23 MB Adobe PDF Visualizza/Apri

I documenti in POLITesi sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/10589/260246