The French transmission grid is undergoing a rapid transformation, driven by the growing penetration of renewable generation connected through grid following converters, which are gradually displacing conventional synchronous generation. This shift is reshaping stability behaviour and giving rise to sub-synchronous oscillations, a phenomenon already observed in weak grids around the world and increasingly relevant to transmission system operators such as RTE. Standard RMS models fail to capture the correct sub-synchronous oscillation frequency and fast control dynamics, forcing reliance on computationally heavy EMT simulations that are impractical for the large scale studies TSOs require. This thesis addresses the question of whether an RMS model of a grid following converter, built on the structure of WECC type models, can reproduce EMT level results for small and large disturbance and large scale transmission studies. An average RMS converter model, implemented in OpenModelica and Dyna$\omega$o, is proposed and validated against EMT simulations and the WECC standard model, across single converter, multi converter, and large scale network test cases. Results show that the proposed model reproduces EMT behaviour with good accuracy for both small and large perturbations on reduced size networks, consistently outperforming the WECC model, and that dynamic line modeling is essential to correctly capture SSO phenomena, as static line representations systematically mask them. Validation on large scale networks remains preliminary due to current Dyna$\omega$o solver limitations, and is identified as a priority for future work.
La rete di trasmissione francese sta cambiando rapidamente, con la crescente integrazione di fonti rinnovabili connesse attraverso convertitori grid-following e la progressiva riduzione della generazione sincrona. Questa trasformazione modifica il comportamento dinamico della rete, facendo emergere nuovi fenomeni tra cui le oscillazioni sub-sincrone, già osservate in reti deboli in diverse parti del mondo e sempre più rilevanti per i gestori dei sistemi di trasmissione, come RTE. I modelli RMS convenzionali non riproducono correttamente la frequenza delle oscillazioni sub-sincrone né le dinamiche rapide dei controlli, rendendo necessario il ricorso a simulazioni EMT, caratterizzate però da un elevato costo computazionale e difficilmente applicabili a studi su larga scala. Questa tesi studia la possibilità di sviluppare un modello RMS di un convertitore grid following, basato sulla struttura dei modelli WECC, in grado di riprodurre risultati a livello EMT per piccole e grandi perturbazioni. Viene proposto un modello medio RMS, implementato in OpenModelica e Dyna$\omega$o, e validato mediante il confronto con simulazioni EMT e con il modello standard WECC su casi a singolo convertitore, multi convertitore e su larga scala. I risultati mostrano che il modello proposto riproduce con buona accuratezza il comportamento EMT per piccole e grandi perturbazioni, risultando più accurato del modello WECC. La modellazione dinamica delle linee è inoltre essenziale per catturare i fenomeni SSO, mentre le linee statiche tendono a mascherarli. La validazione su reti di grandi dimensioni rimane preliminare a causa delle limitazioni del solutore di Dyna$\omega$o e rappresenta una priorità per gli studi futuri.
Modeling grid following converters for sub-synchronous oscillations in large disturbance and large scale studies
Bergamaschi, Gaia
2025/2026
Abstract
The French transmission grid is undergoing a rapid transformation, driven by the growing penetration of renewable generation connected through grid following converters, which are gradually displacing conventional synchronous generation. This shift is reshaping stability behaviour and giving rise to sub-synchronous oscillations, a phenomenon already observed in weak grids around the world and increasingly relevant to transmission system operators such as RTE. Standard RMS models fail to capture the correct sub-synchronous oscillation frequency and fast control dynamics, forcing reliance on computationally heavy EMT simulations that are impractical for the large scale studies TSOs require. This thesis addresses the question of whether an RMS model of a grid following converter, built on the structure of WECC type models, can reproduce EMT level results for small and large disturbance and large scale transmission studies. An average RMS converter model, implemented in OpenModelica and Dyna$\omega$o, is proposed and validated against EMT simulations and the WECC standard model, across single converter, multi converter, and large scale network test cases. Results show that the proposed model reproduces EMT behaviour with good accuracy for both small and large perturbations on reduced size networks, consistently outperforming the WECC model, and that dynamic line modeling is essential to correctly capture SSO phenomena, as static line representations systematically mask them. Validation on large scale networks remains preliminary due to current Dyna$\omega$o solver limitations, and is identified as a priority for future work.| File | Dimensione | Formato | |
|---|---|---|---|
|
Bergamaschi_Gaia_Tesi_2026.pdf
accessibile in internet per tutti
Descrizione: tesi
Dimensione
9.69 MB
Formato
Adobe PDF
|
9.69 MB | Adobe PDF | Visualizza/Apri |
|
Bergamaschi_Gaia_Executive_Summary_2026.pdf
accessibile in internet per tutti
Descrizione: executive summary
Dimensione
3.03 MB
Formato
Adobe PDF
|
3.03 MB | Adobe PDF | Visualizza/Apri |
I documenti in POLITesi sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.
https://hdl.handle.net/10589/265927