The displacement of synchronous generation by converter connected renewable sources reduces both the inertia and the primary regulating power of a power system, and island systems with weak interconnection experience this first. The purpose of this study is to assess how far a battery energy storage system can contain the frequency deviation produced by a real power imbalance, using two control actions: a droop response proportional to the frequency deviation, and a synthetic inertia response proportional to its rate of change. It further examines what each control action contributes to the response, and whether the battery required for the service is limited by its power or by its energy. A fifteen-minute event recorded in the Sardinian power system on 27 September 2018 is reconstructed as a load disturbance derived from the measured generation series, and the recorded frequency is used to check the output of the model. The disturbance is applied to a single bus equivalent model sized from the real dispatch of that hour and implemented in ANDES, an open-source simulation framework, first without storage and then with a battery providing droop alone and droop combined with synthetic inertia. Without storage, the model reproduces the recorded nadir and its timing closely. Droop control reduces the nadir depth by 74.5%, from 418.9 mHz to 106.9 mHz, whereas synthetic inertia lowers the maximum and the root mean square rate of change of frequency while leaving the nadir unchanged. Over the event the battery reaches about two thirds of its rated power, while its state of charge moves by only a few percentage points. Fast frequency regulation of this kind is therefore constrained by converter rating rather than by stored energy, and synthetic inertia should be judged on the rate of change of frequency rather than on the nadir. Each simulation of the fifteen-minute event runs in about six minutes, some two and a half times faster than the event itself, so the model is light enough for serial simulation campaigns and sensitivity analyses.

La sostituzione della generazione sincrona con fonti rinnovabili connesse tramite convertitori riduce sia l’inerzia sia la potenza di regolazione primaria di un sistema elettrico, e i sistemi isolani caratterizzati da interconnessioni deboli sono i primi a risentirne. Il presente studio mira a valutare in quale misura un sistema di accumulo elettrochimico a batteria (Battery Energy Storage System, BESS) possa contenere la deviazione di frequenza prodotta da uno squilibrio di potenza attiva, mediante due azioni di controllo: una risposta di tipo droop proporzionale alla deviazione di frequenza e una risposta di inerzia sintetica proporzionale alla sua derivata temporale. Lo studio esamina inoltre il contributo di ciascuna azione di controllo alla risposta del sistema e verifica se il dimensionamento della batteria necessaria per fornire tale servizio sia determinato dalla potenza o dall’energia disponibile. Un evento della durata di quindici minuti, registrato nel sistema elettrico sardo il 27 settembre 2018, viene ricostruito come una perturbazione di carico derivata dalla serie temporale della generazione misurata, mentre la frequenza registrata viene utilizzata per verificare i risultati del modello. La perturbazione viene applicata a un modello equivalente a singolo nodo, dimensionato sulla base del dispacciamento reale relativo a quell’ora e implementato in ANDES, un framework open-source per la simulazione dei sistemi elettrici. Il sistema viene analizzato dapprima in assenza di accumulo e successivamente con una batteria che fornisce esclusivamente una risposta droop e, in seguito, una combinazione di droop e inerzia sintetica. In assenza di accumulo, il modello riproduce con buona accuratezza il minimo di frequenza registrato e il relativo istante di occorrenza. Il controllo droop riduce l’entità del minimo di frequenza del 74,5%, passando da 418,9 mHz a 106,9 mHz, mentre l’inerzia sintetica riduce sia il valore massimo sia il valore quadratico medio (RMS) del rateo di variazione della frequenza, lasciando invariato il minimo di frequenza. Nel corso dell’evento, la batteria raggiunge circa due terzi della propria potenza nominale, mentre il suo stato di carica varia di soli pochi punti percentuali. La regolazione rapida della frequenza di questo tipo risulta pertanto limitata dalla potenza nominale del convertitore piuttosto che dall’energia immagazzinata, mentre l’efficacia dell’inerzia sintetica dovrebbe essere valutata in relazione al rateo di variazione della frequenza anziché al minimo di frequenza. Ogni simulazione dell’evento di quindici minuti viene eseguita in circa sei minuti, risultando quindi circa due volte e mezzo più veloce dell’evento stesso. Il modello risulta pertanto sufficientemente leggero da consentire campagne di simulazione seriali e analisi di sensibilità.

Key impacts of battery energy storage systems on grid frequency response in low inertia power systems: the case of droop control and synthetic inertia, a time domain simulation analysis

HASSANZADEHKIABI, FARIMA
2026/2027

Abstract

The displacement of synchronous generation by converter connected renewable sources reduces both the inertia and the primary regulating power of a power system, and island systems with weak interconnection experience this first. The purpose of this study is to assess how far a battery energy storage system can contain the frequency deviation produced by a real power imbalance, using two control actions: a droop response proportional to the frequency deviation, and a synthetic inertia response proportional to its rate of change. It further examines what each control action contributes to the response, and whether the battery required for the service is limited by its power or by its energy. A fifteen-minute event recorded in the Sardinian power system on 27 September 2018 is reconstructed as a load disturbance derived from the measured generation series, and the recorded frequency is used to check the output of the model. The disturbance is applied to a single bus equivalent model sized from the real dispatch of that hour and implemented in ANDES, an open-source simulation framework, first without storage and then with a battery providing droop alone and droop combined with synthetic inertia. Without storage, the model reproduces the recorded nadir and its timing closely. Droop control reduces the nadir depth by 74.5%, from 418.9 mHz to 106.9 mHz, whereas synthetic inertia lowers the maximum and the root mean square rate of change of frequency while leaving the nadir unchanged. Over the event the battery reaches about two thirds of its rated power, while its state of charge moves by only a few percentage points. Fast frequency regulation of this kind is therefore constrained by converter rating rather than by stored energy, and synthetic inertia should be judged on the rate of change of frequency rather than on the nadir. Each simulation of the fifteen-minute event runs in about six minutes, some two and a half times faster than the event itself, so the model is light enough for serial simulation campaigns and sensitivity analyses.
ING - Scuola di Ingegneria Industriale e dell'Informazione
20-ott-2026
2026/2027
La sostituzione della generazione sincrona con fonti rinnovabili connesse tramite convertitori riduce sia l’inerzia sia la potenza di regolazione primaria di un sistema elettrico, e i sistemi isolani caratterizzati da interconnessioni deboli sono i primi a risentirne. Il presente studio mira a valutare in quale misura un sistema di accumulo elettrochimico a batteria (Battery Energy Storage System, BESS) possa contenere la deviazione di frequenza prodotta da uno squilibrio di potenza attiva, mediante due azioni di controllo: una risposta di tipo droop proporzionale alla deviazione di frequenza e una risposta di inerzia sintetica proporzionale alla sua derivata temporale. Lo studio esamina inoltre il contributo di ciascuna azione di controllo alla risposta del sistema e verifica se il dimensionamento della batteria necessaria per fornire tale servizio sia determinato dalla potenza o dall’energia disponibile. Un evento della durata di quindici minuti, registrato nel sistema elettrico sardo il 27 settembre 2018, viene ricostruito come una perturbazione di carico derivata dalla serie temporale della generazione misurata, mentre la frequenza registrata viene utilizzata per verificare i risultati del modello. La perturbazione viene applicata a un modello equivalente a singolo nodo, dimensionato sulla base del dispacciamento reale relativo a quell’ora e implementato in ANDES, un framework open-source per la simulazione dei sistemi elettrici. Il sistema viene analizzato dapprima in assenza di accumulo e successivamente con una batteria che fornisce esclusivamente una risposta droop e, in seguito, una combinazione di droop e inerzia sintetica. In assenza di accumulo, il modello riproduce con buona accuratezza il minimo di frequenza registrato e il relativo istante di occorrenza. Il controllo droop riduce l’entità del minimo di frequenza del 74,5%, passando da 418,9 mHz a 106,9 mHz, mentre l’inerzia sintetica riduce sia il valore massimo sia il valore quadratico medio (RMS) del rateo di variazione della frequenza, lasciando invariato il minimo di frequenza. Nel corso dell’evento, la batteria raggiunge circa due terzi della propria potenza nominale, mentre il suo stato di carica varia di soli pochi punti percentuali. La regolazione rapida della frequenza di questo tipo risulta pertanto limitata dalla potenza nominale del convertitore piuttosto che dall’energia immagazzinata, mentre l’efficacia dell’inerzia sintetica dovrebbe essere valutata in relazione al rateo di variazione della frequenza anziché al minimo di frequenza. Ogni simulazione dell’evento di quindici minuti viene eseguita in circa sei minuti, risultando quindi circa due volte e mezzo più veloce dell’evento stesso. Il modello risulta pertanto sufficientemente leggero da consentire campagne di simulazione seriali e analisi di sensibilità.
File allegati
File Dimensione Formato  
ExecutiveSummary_FarimaHassanzadehKiabi.pdf

non accessibile

Dimensione 1.11 MB
Formato Adobe PDF
1.11 MB Adobe PDF   Visualizza/Apri
Thesis_FarimaHassanzadehKiabi.pdf

non accessibile

Dimensione 3.25 MB
Formato Adobe PDF
3.25 MB Adobe PDF   Visualizza/Apri

I documenti in POLITesi sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/10589/266143