Operating district heating networks at the optimal temperature in each interval reduces distribution thermal losses, enhancing the overall system’s efficiency, while also guaranteeing the continuous satisfaction of the thermal demand of all end-users. However, deploying such an operation strategy requires a modeling approach that simultaneously predicts the dynamic behavior of the thermal demand of buildings and of the different components of the system. Motivated by this challenge, the present thesis develops a predictive methodology to determine the minimum feasible plant supply temperature at each interval, while also identifying the substations that impose this operational limit. The methodology operates at a 30-minute temporal resolution using exclusively information available in advance of each decision interval, thereby ensuring its capability of deployment in operational settings. The developed procedure is applied to a district-heating network in the Lombardy region. Three machine learning-driven sub-models predict building thermal demand, the normalized supply-temperature drop between the plant and each substation, and the substation return temperature, while the flow rate is obtained from an energy balance and its mutual dependence with the supply temperature is resolved through an iterative network solution. The results indicate a notable difference between the identified optimal operation temperature and the corresponding measured values in most of the intervals, with a mean absolute difference of approximately 3.7 °C. During daytime operation, the reduction of the plant supply temperature is estimated at 2.5 °C without a safety margin and 1.5 °C with it. During the morning restart, by contrast, the identified temperature exceeds the measured one in most half-hours, which indicates that an earlier restart would improve the service to the most hydraulically constrained substations. No additional reduction is identified during nighttime operation, when the network is already operated at substantially lower supply temperatures. In most half-hours, the critical substation belongs to a set of only three out of the 44 analyzed substations, the most frequent being the substation furthest from the plant. Finally, each degree-hour of supply-temperature reduction is associated with an estimated decrease of 6.17 kWh in distribution heat losses, at the cost of 0.45 kWh of additional electrical consumption of the pumps.

L'esercizio delle reti di teleriscaldamento alla temperatura ottimale in ciascun intervallo riduce le perdite termiche di distribuzione, migliorando l'efficienza complessiva del sistema, e garantisce al tempo stesso il soddisfacimento continuo della domanda termica di tutte le utenze finali. Tuttavia, l'attuazione di una tale strategia di esercizio richiede un approccio modellistico in grado di prevedere simultaneamente il comportamento dinamico della domanda termica degli edifici e dei diversi componenti del sistema. Motivata da questa sfida, la presente tesi sviluppa una metodologia predittiva per determinare, in ciascun intervallo, la temperatura minima ammissibile di mandata della centrale e per identificare le sottostazioni che impongono tale limite operativo. La metodologia opera con una risoluzione temporale di 30 minuti e utilizza esclusivamente informazioni disponibili in anticipo rispetto a ciascun intervallo decisionale, garantendone così l'applicabilità in contesti operativi. La procedura sviluppata è applicata a una rete di teleriscaldamento situata in Lombardia. Tre sottomodelli basati sul machine learning prevedono la domanda termica degli edifici, la caduta normalizzata della temperatura di mandata tra la centrale e ciascuna sottostazione e la temperatura di ritorno della sottostazione, mentre la portata è ricavata da un bilancio energetico e la sua dipendenza reciproca con la temperatura di mandata è risolta mediante una soluzione iterativa della rete. I risultati indicano, nella maggior parte degli intervalli, una differenza rilevante tra la temperatura di esercizio ottimale individuata e i corrispondenti valori misurati, con uno scarto medio assoluto di circa 3,7 °C. Durante l'esercizio diurno, la riduzione della temperatura di mandata della centrale è stimata in 2,5 °C senza margine di sicurezza e in 1,5 °C con il margine. Durante la ripartenza mattutina, al contrario, la temperatura individuata supera quella misurata nella maggior parte degli intervalli semiorari, il che indica che una ripartenza anticipata migliorerebbe il servizio alle sottostazioni più vincolate dal punto di vista idraulico. Non si individua alcuna riduzione aggiuntiva durante l'esercizio notturno, quando la rete è già gestita a temperature di mandata sensibilmente più basse. Nella maggior parte degli intervalli semiorari, la sottostazione critica appartiene a un insieme di sole tre delle 44 sottostazioni analizzate, e la più frequente è la sottostazione più lontana dalla centrale. Infine, a ogni grado-ora di riduzione della temperatura di mandata è associata una diminuzione stimata di 6,17 kWh delle perdite termiche di distribuzione, a fronte di un consumo elettrico aggiuntivo delle pompe di 0,45 kWh.

Adaptive supply temperature optimization for district heating networks through critical substation identification enabled by machine learning-based pipelines

Pinzon Corredor, David Santiago
2025/2026

Abstract

Operating district heating networks at the optimal temperature in each interval reduces distribution thermal losses, enhancing the overall system’s efficiency, while also guaranteeing the continuous satisfaction of the thermal demand of all end-users. However, deploying such an operation strategy requires a modeling approach that simultaneously predicts the dynamic behavior of the thermal demand of buildings and of the different components of the system. Motivated by this challenge, the present thesis develops a predictive methodology to determine the minimum feasible plant supply temperature at each interval, while also identifying the substations that impose this operational limit. The methodology operates at a 30-minute temporal resolution using exclusively information available in advance of each decision interval, thereby ensuring its capability of deployment in operational settings. The developed procedure is applied to a district-heating network in the Lombardy region. Three machine learning-driven sub-models predict building thermal demand, the normalized supply-temperature drop between the plant and each substation, and the substation return temperature, while the flow rate is obtained from an energy balance and its mutual dependence with the supply temperature is resolved through an iterative network solution. The results indicate a notable difference between the identified optimal operation temperature and the corresponding measured values in most of the intervals, with a mean absolute difference of approximately 3.7 °C. During daytime operation, the reduction of the plant supply temperature is estimated at 2.5 °C without a safety margin and 1.5 °C with it. During the morning restart, by contrast, the identified temperature exceeds the measured one in most half-hours, which indicates that an earlier restart would improve the service to the most hydraulically constrained substations. No additional reduction is identified during nighttime operation, when the network is already operated at substantially lower supply temperatures. In most half-hours, the critical substation belongs to a set of only three out of the 44 analyzed substations, the most frequent being the substation furthest from the plant. Finally, each degree-hour of supply-temperature reduction is associated with an estimated decrease of 6.17 kWh in distribution heat losses, at the cost of 0.45 kWh of additional electrical consumption of the pumps.
ING - Scuola di Ingegneria Industriale e dell'Informazione
20-ott-2026
2025/2026
L'esercizio delle reti di teleriscaldamento alla temperatura ottimale in ciascun intervallo riduce le perdite termiche di distribuzione, migliorando l'efficienza complessiva del sistema, e garantisce al tempo stesso il soddisfacimento continuo della domanda termica di tutte le utenze finali. Tuttavia, l'attuazione di una tale strategia di esercizio richiede un approccio modellistico in grado di prevedere simultaneamente il comportamento dinamico della domanda termica degli edifici e dei diversi componenti del sistema. Motivata da questa sfida, la presente tesi sviluppa una metodologia predittiva per determinare, in ciascun intervallo, la temperatura minima ammissibile di mandata della centrale e per identificare le sottostazioni che impongono tale limite operativo. La metodologia opera con una risoluzione temporale di 30 minuti e utilizza esclusivamente informazioni disponibili in anticipo rispetto a ciascun intervallo decisionale, garantendone così l'applicabilità in contesti operativi. La procedura sviluppata è applicata a una rete di teleriscaldamento situata in Lombardia. Tre sottomodelli basati sul machine learning prevedono la domanda termica degli edifici, la caduta normalizzata della temperatura di mandata tra la centrale e ciascuna sottostazione e la temperatura di ritorno della sottostazione, mentre la portata è ricavata da un bilancio energetico e la sua dipendenza reciproca con la temperatura di mandata è risolta mediante una soluzione iterativa della rete. I risultati indicano, nella maggior parte degli intervalli, una differenza rilevante tra la temperatura di esercizio ottimale individuata e i corrispondenti valori misurati, con uno scarto medio assoluto di circa 3,7 °C. Durante l'esercizio diurno, la riduzione della temperatura di mandata della centrale è stimata in 2,5 °C senza margine di sicurezza e in 1,5 °C con il margine. Durante la ripartenza mattutina, al contrario, la temperatura individuata supera quella misurata nella maggior parte degli intervalli semiorari, il che indica che una ripartenza anticipata migliorerebbe il servizio alle sottostazioni più vincolate dal punto di vista idraulico. Non si individua alcuna riduzione aggiuntiva durante l'esercizio notturno, quando la rete è già gestita a temperature di mandata sensibilmente più basse. Nella maggior parte degli intervalli semiorari, la sottostazione critica appartiene a un insieme di sole tre delle 44 sottostazioni analizzate, e la più frequente è la sottostazione più lontana dalla centrale. Infine, a ogni grado-ora di riduzione della temperatura di mandata è associata una diminuzione stimata di 6,17 kWh delle perdite termiche di distribuzione, a fronte di un consumo elettrico aggiuntivo delle pompe di 0,45 kWh.
File allegati
File Dimensione Formato  
Thesis David Santiago Pinzon - 10934863 - Final.pdf

non accessibile

Descrizione: This thesis develops a deployable predictive methodology that combines machine learning-driven sub-models with an energy balance to determine, every half-hour, the minimum feasible plant supply temperature of a district heating network and the critical substations that set it. Applied to a legacy third-generation network in Lombardy, it estimates a daytime reduction of the plant supply temperature of approximately 1.5 °C with the safety margin.
Dimensione 1.69 MB
Formato Adobe PDF
1.69 MB Adobe PDF   Visualizza/Apri
Executive Summary - David Santiago Pinzon - 10934863.pdf

non accessibile

Descrizione: This executive summary presents, in six pages, the predictive methodology developed in the thesis to determine the minimum feasible plant supply temperature of a district heating network every half-hour and its application to a legacy third-generation network in Lombardy. It summarizes the main results, including the estimated daytime reduction of the plant supply temperature, the three critical substations and the energy associated with each degree-hour of reduction.
Dimensione 392.59 kB
Formato Adobe PDF
392.59 kB Adobe PDF   Visualizza/Apri

I documenti in POLITesi sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/10589/266516